Fire extinguisher servicing: keeping them usable, not just present

Fire extinguishers need annual service and periodic overhaul. What each check covers, how to decide type and placement, and the records inspectors ask for.

How-toF

Fire extinguisher servicing is the annual check by a competent person that each unit is charged, undamaged and ready to work. Extinguishers are the most visible fire precaution in any building and the least thought about — they hang on a wall for a decade and nobody asks whether they would actually discharge.

What fire extinguisher servicing covers

  • Pressure check, confirming the gauge reads within range and the unit has not slowly discharged.
  • External condition: corrosion, dents, and a hose or horn that has perished.
  • Safety pin and tamper indicator intact, which also tells you whether it has been used.
  • Weight check against the stated charge, which catches slow loss that a gauge may not show.
  • Operating instructions legible and facing outward.
  • Mounting secure and at the correct height, with the unit in its designated place.
  • A service label recording the date, the engineer and the next due date.

Beyond the annual check

Water and foam extinguishers typically need an extended service every five years, where the unit is discharged, examined internally and recharged — the annual check cannot see inside. Carbon dioxide units generally need a pressure test on a longer cycle, often ten years, because they are high-pressure vessels. Both are regularly missed, since the annual service happens like clockwork while the longer cycles fall outside anyone's routine and nobody is tracking a ten-year date.

Type matters more than quantity. A water extinguisher next to an electrical panel is worse than nothing, and foam on a cooking oil fire can spread it. Getting the right type in the right place is a judgement from the fire risk assessment, not a matter of covering the building evenly.

The records inspectors ask for

  1. An inventory with each unit's location, type, size and serial number.
  2. Annual service dates with the engineer's details and any defects found.
  3. Extended service and pressure test dates, which is where the gaps usually are.
  4. Monthly visual checks by staff, confirming each unit is in place, unobstructed and showing correct pressure.
  5. Replacement records, since a replaced unit resets its own service cycle.
  6. Discharge records, because a used extinguisher must be recharged rather than put back.

Ettex Records keeps the inventory with annual, extended and pressure-test dates per unit, which makes the long cycles visible instead of forgotten. The monthly visual checks sit alongside the other recurring building checks, since they are reviewed together.

Frequently asked

How often must extinguishers be serviced?

An annual service by a competent person, plus an extended service for water and foam units — commonly every five years — and a pressure test for CO2 units on a longer cycle.

What is usually missed?

The extended service and pressure test cycles. The annual check happens reliably; the five and ten-year dates fall outside anyone's routine.

Does extinguisher type matter?

Considerably. Water near electrical equipment or foam on cooking oil makes things worse — type and placement follow the fire risk assessment.