Smoke control: keeping escape routes usable

Smoke control keeps smoke out of the routes people use to leave. The systems involved, what they depend on, and why smoke kills before fire does.

How-toS

Smoke control keeps smoke away from the routes people need to use. It matters more than its profile suggests: in building fires the great majority of deaths are caused by smoke inhalation rather than burns, and people are overcome in corridors and stairwells they could otherwise have walked down.

What smoke control systems do

  • Natural ventilation: openable vents at high level that let smoke escape by buoyancy.
  • Mechanical extract that pulls smoke out of a corridor or lobby at a designed rate.
  • Pressure differential systems that hold a stairwell at higher pressure so smoke cannot enter.
  • Smoke curtains and reservoirs that contain smoke at ceiling level rather than letting it spread.
  • Automatic opening vents in stairs, triggered by detection or operated by the fire service.
  • Dampers in ductwork that close to stop smoke travelling through the ventilation system.

What these systems depend on

Doors being closed, mostly. A pressurisation system is designed around a specific number of doors open at once, and a wedged lobby door can defeat it entirely — the pressure escapes through the opening and smoke enters the stair as if nothing had been installed. The same applies to natural systems, which need an inlet as well as an outlet: a vent at the top does nothing if air cannot enter below. These dependencies are invisible to occupants, which is why systems get defeated by people acting reasonably.

Smoke control is usually part of a wider fire strategy, and altering one element without reference to it can nullify the rest. A new partition that changes airflow in a corridor is a smoke control matter even though nobody doing the work would describe it that way.

Testing and what gets missed

  1. Weekly or monthly function tests depending on the system, confirming vents open and fans start.
  2. Annual performance testing against the design criteria, not just confirmation that something moved.
  3. Checking the inlet path as well as the extract, since blocked inlets are a common and invisible failure.
  4. Verifying cause-and-effect: the right zone should activate, not merely some zone.
  5. Testing with the building in its real state, including doors that occupants normally leave closed.
  6. Recording measured figures rather than a pass mark, so degradation over years becomes visible.

Ettex Records keeps the test results with their measured values and the design criteria they are judged against, which is what makes a slow decline noticeable. The fire strategy defining what the system is for belongs in the same file.

Frequently asked

Why does smoke control matter so much?

Most fire deaths are from smoke inhalation rather than burns, and smoke makes escape routes unusable long before fire reaches them.

What defeats a pressurisation system?

Doors held open. The system is designed around a set number of open doors, and a wedged lobby door lets the pressure escape and smoke in.

What is most often missed in testing?

The air inlet path, and testing against design criteria rather than simply confirming that fans start and vents open.